4 First Industrial Plug and Play Wall Mount Transmitter/Transducer
4 Triple Isolated:
Inputs to Outputs
Inputs to Power
Outputs to Power
4 Accepts most common input signals
AC Volts, AC Amps RMS, and Line Frequency
4 5 Amp input has a built-in automatic current loop shorting connector to prevent open load when unplug from the base.
4 Active, isolated 4-20mA analog output.
4 Auto sensing AC/DC power supply: 85-265 VAC / 95-370 VDC or optional 14-48 VAC / 10-72 VDC.
4 Accuracy: 0.1% of full scale
Operating Temperature range: 0 to 50 oC Response time: <135msec
4 Plug and Play. Eliminate errors prone re-wiring.
5 4
VOLTAGE Input
Base station needs only one time wiring. TRANSDUCER 0 ~150VAC RMS
Unplug transducers for easy batch routine calibration.
Application Examples:
Motor Generator-Set Frequency Control
The analog output is scaled at 55 Hz for 4 mA and 65 Hz for 20 mA.
The speed control actuator is set to 12 mA to govern the speed at a generator output of 60.0 Hz.
If the frequency falls below 60.0 Hz, the motor speed increases.
If the frequency rises above 60.0 Hz, the motor speed decreases.
TDX-HZ
transducer
4-20 mA output for speed control
A motor generator set that requires to be controlled at 60 Hz output frequency.
For Product Details, Please Visit www.texmate.com
Quick & Easy Calibration Steps:
1)- Remove Power from the transducer.
2)- For batch calibration, unplug the transducer from the base unit that has been mounted in the equiptment.
3)- Plug the transducer into master calibration base station.
4)- Apply specified power ranges to transducer terminals 3 and 4.
5)- Apply input signal based on the model number to transducer terminals 6 and 5.
6)- Apply Minimum Input and adjust zero pot so output reads 4mA between terminals 2 (+) and 1 (-)
7)- Apply Maximum Input and adjust Span pot so output reads 20mA on terminals 2 (+) and 1 (-).
4 to 20mA Calibrator
Single or batch calibration made easy. No messy, error-prone re-wiring, no down-time.
Calibration Base Station
4 Three models to choose from:
TDX-ACATrue RMS AC current measurement.
Input full scale: 0 to 5A AC RMS; Outout: 4 to 20mA DC
TDX-ACVInput measurement range: 0 to 150VRMS; Output: 4 to 20mA DC
TDX-HZInput type: AC voltage. Measurement type: line frequency.
Input voltage range: 15 to 350VRMS; Full scale: 55Hz to 65Hz;
Output: 4 to 20mA DC
Transducer Dimensions
Application Examples:
AC Current Measurement and Transmitter
The log feed amperage is measured and re-transmitted via The log feed amperage is measured and re-transmitted via an isolated 4-20 mA analog output that can be sent to a motor controller or a PLC in order to control the motors speed. an isolated 4-20 mA analog output that can be sent to a motor controller or a PLC in order to control the motors speed.
Page 2
Texmate is an American manufacturer of high durability industrial grade panel meters, bar graphs, and transducers. Texmate's meters are frequently equipped with relays and various signal outputs for industrial automation applications and are known for their extremely long service life.